Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2021, 07:56 AM
  • H 0253_H 0252_08202021_010656.mp4

Date
08/20/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10676
Time
12:56 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9241
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0253
Downstream MH
H 0252
Dir. of Survey
Downstream
Length Surveyed
321.7 ft.
Total Length
321.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
3L00
O&M Rating
189
Overall Index
3
Overall Quick
Overall Rating
191
Pipe schematic from manhole H 0253 to H 0252
MH: H 0253MH: H 0252downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02530 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"30.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"59.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.4 ft. CS - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES198.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.3 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish321.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE321.7 ft. AMH - Downstream Manhole, Survey Ends - H 0252

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

    164.4 ft. - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
258.2TFA
0MGOCOCKROACHES IN MANHOLE
59.3TF
101.7TFC
0MWM
321.7MGOCOCKROACHES IN MANHOLE
0AMHH 0253
201.6TFA
321.7AMHH 0252
164.4CS
116.9TFC
8.7TFA
56.8TFC
30.8TF
2DAGS
198.4TF
0MWL
319.3DAGS
261.8TFC

Properties (7)

additional_info
630069081921201
custom_field_three
GREASE
custom_field_two
3
customer
1
datetime
2021-08-20T00:56:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false