Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 04:38 AM
  • H 0249_H 0248A_08232021_214414.mp4

Date
08/23/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10672
Time
9:38 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9243
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0249
Downstream MH
H 0248A
Dir. of Survey
Downstream
Length Surveyed
117.7 ft.
Total Length
117.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole H 0249 to H 0248A
MH: H 0249MH: H 0248Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 02492 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start81.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"84 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.7 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish117.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE117.7 ft. AMH - Downstream Manhole, Survey Ends - H 0248A117.7 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    117.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
117.7MGOCOCKROACHES IN MANHOLE
117.7AMHH 0248A
84TFC
115.7DAGS
0MWL
0MWM
0MGOCOCKROACHES IN MANHOLE
2DAGS
117.7MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0AMHH 0249
81.4TFC

Properties (7)

additional_info
630069082321201
custom_field_three
GREASE
custom_field_two
3
customer
1
datetime
2021-08-23T21:38:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false