Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2021, 08:30 AM
  • 32 0139_32 0138_08122021_014335.mp4

Date
08/12/2021
W/O
906781
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19887
Time
1:30 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9231
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_906781_TV32015_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0139
Downstream MH
32 0138
Dir. of Survey
Downstream
Length Surveyed
556.7 ft.
Total Length
556.7 ft.
Structural Index
3
Structural Quick
3U00
Structural Rating
333
O&M Index
2
O&M Quick
2U00
O&M Rating
222
Overall Index
3
Overall Quick
Overall Rating
555
Pipe schematic from manhole 32 0139 to 32 0138
MH: 32 0139MH: 32 0138downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01390 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start555.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish555.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish556.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE556.7 ft. AMH - Downstream Manhole, Survey Ends - 32 0138

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    556.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0AMH32 0139
0MWM
0MGOCOCKROACHES IN MANHOLE
556.7MGOCOCKROACHES IN MANHOLE
2DAGS
555.1DAGS
556.7AMH32 0138
555.1SAP
2SAP
0MWL

Properties (7)

additional_info
630069081121202
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-08-12T01:30:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false