Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 09:53 AM
  • 32 0130_32 0129_08132021_030645.mp4

Date
08/13/2021
W/O
906781
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19876
Time
2:53 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9235
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_906781_TV32015_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0130
Downstream MH
32 0129
Dir. of Survey
Downstream
Length Surveyed
475.3 ft.
Total Length
475.3 ft.
Structural Index
3
Structural Quick
3R2R
Structural Rating
470
O&M Index
2
O&M Quick
412R
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
662
Pipe schematic from manhole 32 0130 to 32 0129
MH: 32 0130MH: 32 0129downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01300 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start473.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish473.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish473.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish475.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE475.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0129

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    475.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
473.5SSS
0MGOCOCKROACHES IN MANHOLE
475.3MGOCOCKROACHES IN MANHOLE
0MWM
475.3AMH32 0129
2DAGS
2SSS
473.5DAGS
473.5SAP
2SAP
0AMH32 0130
0MWL

Properties (7)

additional_info
630069081221203
custom_field_three
PROJECTING AGGREGATE/ SPALLING
custom_field_two
2
customer
1
datetime
2021-08-13T02:53:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false