Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2021, 08:59 AM
  • 32 0153_32 0152_08172021_020444.mp4

Date
08/17/2021
W/O
906781
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19904
Time
1:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9238
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_906781_TV32015_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0153
Downstream MH
32 0152
Dir. of Survey
Downstream
Length Surveyed
108.5 ft.
Total Length
108.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
63
O&M Index
2
O&M Quick
412C
O&M Rating
46
Overall Index
3
Overall Quick
Overall Rating
109
Pipe schematic from manhole 32 0153 to 32 0152
MH: 32 0153MH: 32 0152downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01530 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start106.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish106.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish108.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0152108.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    108.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0AMH32 0153
2DAGS
108.5AMH32 0152
2SAP
0MWL
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
108.5MGOCOCKROACHES IN MANHOLE
106.5DAGS
106.5SAP

Properties (7)

additional_info
630069081621201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-08-17T01:59:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false