Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2021, 09:18 AM
  • 32 0150A_32 0150_08172021_022310.mp4

Date
08/17/2021
W/O
906781
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19901
Time
2:18 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9238
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_906781_TV32015_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0150A
Downstream MH
32 0150
Dir. of Survey
Downstream
Length Surveyed
89.8 ft.
Total Length
89.8 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
51
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
3
Overall Quick
Overall Rating
85
Pipe schematic from manhole 32 0150A to 32 0150
MH: 32 0150AMH: 32 0150downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 32 0150A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start87.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish87.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish89.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE89.8 ft. AMH - Downstream Manhole, Survey Ends - 32 0150

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    89.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MWM
89.8MGOCOCKROACHES IN MANHOLE
89.8AMH32 0150
0MWL
2SAP
0MGOCOCKROACHES IN MANHOLE
0AMH32 0150A
87.5SAP
0MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
87.5DAGS

Properties (7)

additional_info
630069081621201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-08-17T02:18:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false