Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2021, 05:28 AM
  • 32 0147_32 0146_08172021_224124.mp4

Date
08/17/2021
W/O
906781
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19896
Time
10:28 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9239
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_906781_TV32015_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0147
Downstream MH
32 0146
Dir. of Survey
Downstream
Length Surveyed
455.4 ft.
Total Length
455.4 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
270
O&M Index
2
O&M Quick
412Q
O&M Rating
184
Overall Index
3
Overall Quick
Overall Rating
454
Pipe schematic from manhole 32 0147 to 32 0146
MH: 32 0147MH: 32 0146downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01470 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start453.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish453.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish455.4 ft. AMH - Downstream Manhole, Survey Ends - 32 0146455.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    455.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
453.7DAGS
455.4AMH32 0146
0MWL
2SAP
453.7SAP
2DAGS
455.4MGOCOCKROACHES IN MANHOLE
0AMH32 0147
0MGOCOCKROACHES IN MANHOLE
0MWM

Properties (7)

additional_info
630069081721201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-08-17T22:28:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false