- Date
- 07/12/2021
- W/O
- 896356
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00709
- PipeID
- P14703
- Time
- 10:48 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Heavy Cleaning
- Media Label
- K9071
- Sewer Name
- 18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
- City
- NORWALK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 37A
- Purpose
- Routine Assessment
- Project
- WO_896356_TV18101_JUN2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 51 in.
- Width
- 51 in.
- Upstream MH
- 18 0848
- Downstream MH
- 18 0847
- Dir. of Survey
- Downstream
- Length Surveyed
- 702.2 ft.
- Total Length
- 702.2 ft.
- Structural Index
- 3
- Structural Quick
- 5I3[
- Structural Rating
- 960
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 960
Pipe schematic from manhole 18 0848 to 18 0847 Observation photos (4)

2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

700.5 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES