Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2021, 09:10 AM
  • 22 1124_22 0924_09082021_023345.mp4

Date
09/08/2021
W/O
911864
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00820
PipeID
P17505
Time
2:10 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9262
Sewer Name
22 POLYMER PLANT WASTE WATER DISPOSAL LINE
City
IRWINDALE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_911864_TV22080_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
22 1124
Downstream MH
22 0924
Dir. of Survey
Downstream
Length Surveyed
325.5 ft.
Total Length
325.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3122
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 22 1124 to 22 0924
MH: 22 1124MH: 22 0924downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 11243 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start91.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"123.5 ft. RFJ - Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YES129.7 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES145.3 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES145.3 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES167.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"171.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"239.7 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start245 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"295.3 ft. RPR - Repair Pipe Replaced, within 8 inches of joint: YES - PVC310.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"325.1 ft. TBI - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"325.5 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish325.5 ft. MSA - Survey Abandoned - INTRUDING LATERAL325.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YES

    123.5 ft. - Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

    129.7 ft. - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES

    145.3 ft. - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    145.3 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    239.7 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    310.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    325.1 ft. - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

Observations (19)

DistanceCodeObservation
3DAGS
129.7RFJ
171.3TB
325.5DAZ
0MWL
239.7DAZ
325.1TBI
325.5MSAINTRUDING LATERAL
245TB
295.3RPRPVC
91.2TB
145.3RFJ
145.3FS
0MWM
167.8TB
123.5RFJ
325.5DAGS
0AMH22 1124
310.3TB

Properties (8)

additional_info
630138090721201
custom_field_three
BROKEN PIPE
custom_field_two
2
customer
1
datetime
2021-09-08T02:10:24-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27163