Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 10:40 AM
  • 22 0924_22 1123_09082021_040236.mp4

Date
08/24/2021
W/O
911864
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00820
PipeID
P17504
Time
3:40 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9262
Sewer Name
22 POLYMER PLANT WASTE WATER DISPOSAL LINE
City
IRWINDALE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_911864_TV22080_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
22 0924
Downstream MH
22 1123
Dir. of Survey
Downstream
Length Surveyed
195 ft.
Total Length
195 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 22 0924 to 22 1123
MH: 22 0924MH: 22 1123downstream0 ft. MWL - Water Level, 0 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09240 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - STOP LOG IN MH18.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start41.1 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"41.3 ft. CS - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES72.3 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES86.6 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES193.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish195 ft. AMH - Downstream Manhole, Survey Ends - 22 1123

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    18.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    72.3 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    86.6 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
86.6CS
0MWL
41.3CS
195AMH22 1123
0AMH22 0924
193.7DAGS
0MWM
72.3CS
41.1TB
18.9DAGS
0MGOSTOP LOG IN MH

Properties (8)

additional_info
630138090721201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-08-24T03:40:28-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27163