Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 05:18 AM
  • H 0994_H 0993_08122021_223404.mp4

Date
08/12/2021
W/O
906779
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01005
PipeID
P15408
Time
10:18 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9117
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_906779_TV21087_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0994
Downstream MH
H 0993
Dir. of Survey
Downstream
Length Surveyed
325.8 ft.
Total Length
325.8 ft.
Structural Index
2
Structural Quick
3D2L
Structural Rating
209
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
337
Pipe schematic from manhole H 0994 to H 0993
MH: H 0994MH: H 0993downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 09942 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - 45% MAG COAT111.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN146 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN190 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start232.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN286 ft. MWM - Water Mark, 20 %of cross sectional area323 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish324.8 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish324.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE324.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE325 ft. MGO - General Observation - ROACHES @ MH325.8 ft. AMH - Downstream Manhole, Survey Ends - H 0993

Observation photos (6)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 45% MAG COAT

    2.6 ft. - General Observation - 45% MAG COAT

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    111.4 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    146 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    190 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    232.4 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

Observations (18)

DistanceCodeObservation
146TBOPEN
286MWM
0MWL
2DAGS
324.8SSS
0MWM
0AMHH 0994
324.9MGOCONN @ MH 3 O'CLOCK/ACTIVE
324.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
190SAV
111.4TBOPEN
325.8AMHH 0993
2.6SSS
232.4TBOPEN
325MGOROACHES @ MH
324.8SAV
2.6MGO45% MAG COAT
323DAGS

Properties (7)

additional_info
630138081221201
custom_field_three
MAG COAT, SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-08-12T22:18:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false