Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2021, 06:11 PM
  • H 0980_H 0979_08162021_112734.mp4

Date
08/16/2021
W/O
906779
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01005
PipeID
P15393
Time
11:11 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9254
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_906779_TV21087_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0980
Downstream MH
H 0979
Dir. of Survey
Downstream
Length Surveyed
401.8 ft.
Total Length
401.8 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
397
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
401
Pipe schematic from manhole H 0980 to H 0979
MH: H 0980MH: H 0979downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - H09802 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. MGO - General Observation - 70% MAG COAT291.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 4"399 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish399.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish401.8 ft. AMH - Downstream Manhole, Survey Ends - H 0979

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2DAGS
0MWM
399.9SAV
399DAGS
0MWL
3.8MGO70% MAG COAT
291.2TFA
399.9SSS
0MGOCONN @ MH 9 O'CLOCK/OPEN
2SSS
0AMHH0980
401.8AMHH 0979
2.5SAV

Properties (7)

additional_info
630138081621061
custom_field_three
SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-08-16T11:11:40-07:00
documentation
PROPIPE
is_lateral_inspection
false