Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2021, 06:09 PM
  • 29 0504A_29 0504_07282021_112358.mp4

Date
07/28/2021
W/O
901244
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01090
PipeID
P24554
Time
11:09 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9089
Sewer Name
29 ALAMITOS PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
WO_901244_TV29015_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0504A
Downstream MH
29 0504
Dir. of Survey
Downstream
Length Surveyed
162 ft.
Total Length
162 ft.
Structural Index
3
Structural Quick
413E
Structural Rating
102
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
102
Pipe schematic from manhole 29 0504A to 29 0504
MH: 29 0504AMH: 29 0504downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 0504A3.7 ft. MGO - General Observation - PIPE IS NRCP3.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start80.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES145.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.9 ft. FM - Fracture Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES162 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish162 ft. AMH - Downstream Manhole, Survey Ends - 29 0504162 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    80.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES

    146.9 ft. - Fracture Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
162SAV
145.7TF
162AMH29 0504
0MWM
80.2CL
0MWL
3.7MGOPIPE IS NRCP
3.7SAV
146.9FM
162MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH29 0504A

Properties (7)

additional_info
630074072821052
custom_field_three
AGGREGATE VISIBLE/CRACKS
custom_field_two
3
customer
1
datetime
2021-07-28T11:09:02-07:00
documentation
PROPIPE
is_lateral_inspection