Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2021, 08:22 AM
  • 18 0647_18 0646_06252021_013622.mp4

Date
06/25/2021
W/O
896146
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00692
PipeID
P14497
Time
1:22 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9056
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_896146_TV18085_JUN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0647
Downstream MH
18 0646
Dir. of Survey
Downstream
Length Surveyed
612.7 ft.
Total Length
612.7 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0647 to 18 0646
MH: 18 0647MH: 18 0646downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06470 ft. MWL - Water Level, 10 %of cross sectional area47.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"103.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"170.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"253.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"270.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"332 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"470.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES492.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES497.6 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES612.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0646

Observation photos (3)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    470.8 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    492.7 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    497.6 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
253.7TFC
332TF
47.7TFC
0MWM
170.2TFC
103.3TFC
0AMH18 0647
0MWL
497.6CM
612.7AMH18 0646
270.5TFC
470.8CL
492.7CL

Properties (7)

additional_info
630074062421202
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-06-25T01:22:12-07:00
documentation
PROPIPE
is_lateral_inspection
false