Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2021, 06:27 AM
  • 22 0567_22 0566_09082021_233726.mp4

Date
09/08/2021
W/O
911392
Weather
Dry
Operator/Surveyor
J.BUENROSTRO
Sewer ID
Z00791
PipeID
P16913
Time
11:27 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9263
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_911392_TV22102_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0567
Downstream MH
22 0566
Dir. of Survey
Downstream
Length Surveyed
244.9 ft.
Total Length
244.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0567 to 22 0566
MH: 22 0567MH: 22 0566downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 05670 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start29.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"104.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"179.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"234.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"242.9 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish244.9 ft. AMH - Downstream Manhole, Survey Ends - 22 0566244.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK244.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
234.5TFC
0AMH22 0567
244.9AMH22 0566
29.3TFC
2.1SAP
244.9MGOCONNECTION AT MH 9 O'CLOCK
179.4TFC
0MWM
0MWL
104.6TFC
242.9SAP
244.9MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630138090821201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-09-08T23:27:00-07:00
documentation
PROPIPE
is_lateral_inspection
false