Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2021, 05:36 AM
  • 22 0565A_22 0565Z_09082021_224742.mp4

Date
09/08/2021
W/O
911392
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00791
PipeID
P16910
Time
10:36 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9263
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_911392_TV22102_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0565A
Downstream MH
22 0565Z
Dir. of Survey
Downstream
Length Surveyed
225 ft.
Total Length
225 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0565A to 22 0565Z
MH: 22 0565AMH: 22 0565Zdownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0565A0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.5 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start33.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"54 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"114.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"159.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"199.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"204.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"223.3 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish225 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK225 ft. AMH - Downstream Manhole, Survey Ends - 22 0565Z

Observation photos (1)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
159.2TF
2.5SAP
0MWM
33.9TFC
0AMH22 0565A
0MGOCONNECTION AT MH 3 O'CLOCK
54TFC
225MGOCONNECTION AT MH 9 O'CLOCK
199.4TFC
223.3SAP
204.5TFC
114.3TFC
225AMH22 0565Z

Properties (7)

additional_info
630138090821201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-09-08T22:36:20-07:00
documentation
PROPIPE
is_lateral_inspection
false