Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2021, 08:36 AM
  • 22 0534A_22 0534_09092021_014817.mp4

Date
09/09/2021
W/O
911392
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00791
PipeID
P16876
Time
1:36 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9263
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_911392_TV22102_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0534A
Downstream MH
22 0534
Dir. of Survey
Downstream
Length Surveyed
257.6 ft.
Total Length
257.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0534A to 22 0534
MH: 22 0534AMH: 22 0534downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0534A1.7 ft. MGO - General Observation - MAG COATING1.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"44.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"84 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"88.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"140.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"144.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"192.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"197.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"240.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"245.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"255.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish257.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0534

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
40TFC
140.3TFC
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
192.5TFC
0MWM
255.7SAP
88.2TFC
144.7TFC
84TFC
1.7MGOMAG COATING
257.6AMH22 0534
240.9TFC
44.5TFC
1.7SAP
197.1TFC
245.2TFC
0AMH22 0534A

Properties (7)

additional_info
630138090821201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-09-09T01:36:24-07:00
documentation
PROPIPE
is_lateral_inspection
false