Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2021, 10:55 AM
  • 22 0514_22 0513_09092021_042147.mp4

Date
09/09/2021
W/O
911392
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00791
PipeID
P16854
Time
3:55 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9263
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_911392_TV22102_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0514
Downstream MH
22 0513
Dir. of Survey
Downstream
Length Surveyed
398.8 ft.
Total Length
398.8 ft.
Structural Index
3
Structural Quick
3724
Structural Rating
29
O&M Index
2
O&M Quick
2Q00
O&M Rating
176
Overall Index
2
Overall Quick
Overall Rating
205
Pipe schematic from manhole 22 0514 to 22 0513
MH: 22 0514MH: 22 0513downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9'OCLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 22 05141.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start56.5 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES63.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"68.1 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"86.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES116.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES118.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES211.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: NO213.5 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"218.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.4 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES261.5 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES262.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"277 ft. FS - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES297.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES313.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"363.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"368.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"376.5 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES391.4 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES396.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish398.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0513

Observation photos (13)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: NO

    1.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    56.5 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    86.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    116.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    181.5 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: NO

    211.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    221.4 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    261.5 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    277 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    297.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    376.5 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    391.4 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (33)

DistanceCodeObservation
86.5CM
68.1TBC
261.5CM
63.2TB
318.6TB
213.5TBC
391.4CS
4.1DAGS
313.4TBC
398.8AMH22 0513
123.1TBC
268.1TBA
0MWL
396.5DAGS
118.3TBC
1.2DAGS
221.4CM
163TBC
181.5CM
363.3TBC
368.3TBA
56.5CM
0MWM
376.5CM
297.4CL
0MGOCONNECTION AT MH 9'OCLOCK CAPPED
173.4TB
0AMH22 0514
277FS
218.6TBC
116.4CS
262.8TBC
211.8CL

Properties (7)

additional_info
630138090821201
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2021-09-09T03:55:05-07:00
documentation
PROPIPE
is_lateral_inspection
false