Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2021, 07:15 AM
  • B 0801_B 0800_09082021_002939.mp4

Date
09/08/2021
W/O
911403
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00112
PipeID
P09268
Time
12:15 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9124
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
TEMPLE CITY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_911403_TV15210_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
18 in.
Upstream MH
B 0801
Downstream MH
B 0800
Dir. of Survey
Downstream
Length Surveyed
381.3 ft.
Total Length
381.3 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
525
Pipe schematic from manhole B 0801 to B 0800
MH: B 0801MH: B 0800downstream0 ft. MGO - General Observation - CONN @ MH 8 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 08012 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 55% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start378.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish378.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish379 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish381 ft. MGO - General Observation - ROACHES @ MH381.3 ft. AMH - Downstream Manhole, Survey Ends - B 0800

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 55% MAG COAT

    2 ft. - General Observation - 55% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2DAGS
378.3SAV
378.1SSS
0MGOCONN @ MH 8 O'CLOCK/ACTIVE
379DAGS
0MGOROACHES @ MH
0MWM
2SAV
381MGOROACHES @ MH
2MGO55% MAG COAT
2SSS
381.3AMHB 0800
0MWL
0AMHB 0801

Properties (7)

additional_info
630069090721201
custom_field_three
SPALLING, AGGREGATE VISIBLE, MAG COAT
custom_field_two
3
customer
1
datetime
2021-09-08T00:15:55-07:00
documentation
PRO PIPE
is_lateral_inspection
false