Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 08:54 AM
  • 30 0359_30 0358A_08132021_020514.mp4

Date
08/13/2021
W/O
906363
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00854
PipeID
P26790
Time
1:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9315
Sewer Name
30 CLIFTON P.P. FORCE MAIN GRAVITY TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
District
District 30
Page No.
07
Purpose
Routine Assessment
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Other
Height
10 in.
Upstream MH
30 0359
Downstream MH
30 0358A
Dir. of Survey
Downstream
Length Surveyed
173.9 ft.
Total Length
173.9 ft.
Structural Index
3
Structural Quick
423F
Structural Rating
110
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
110
Pipe schematic from manhole 30 0359 to 30 0358A
MH: 30 0359MH: 30 0358Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 03590 ft. MWM - Water Mark, 5 %of cross sectional area4.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"169 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start169.5 ft. H - Hole, from 04 to 05 o'clock, within 8 inches of joint: YES173.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK173.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish173.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish173.9 ft. AMH - Downstream Manhole, Survey Ends - 30 0358A

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    23.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    169 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, from 04 to 05 o'clock, within 8 inches of joint: YES

    169.5 ft. - Hole, from 04 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
173.9MGOCONNECTION AT THE MH 3 OC'LOCK
23.2TB
0MWL
173.9CM
169.5H
173.9FM
4.8CM
169FM
0AMH30 0359
0MWM
173.9AMH30 0358A

Properties (7)

additional_info
630074081221202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-13T01:54:06-07:00
documentation
PROPIPE
is_lateral_inspection
false