Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 08:44 AM
  • 30 0360_30 0359_08132021_015353.mp4

Date
08/13/2021
W/O
906363
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00854
PipeID
P17996
Time
1:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9315
Sewer Name
30 CLIFTON P.P. FORCE MAIN GRAVITY TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_906363_TV30011_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0360
Downstream MH
30 0359
Dir. of Survey
Downstream
Length Surveyed
211 ft.
Total Length
211 ft.
Structural Index
4
Structural Quick
4G31
Structural Rating
163
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
163
Pipe schematic from manhole 30 0360 to 30 0359
MH: 30 0360MH: 30 0359downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 03604.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish10.6 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start120.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Finish211 ft. AMH - Downstream Manhole, Survey Ends - 30 0359

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    120.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    146.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    161.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    205.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
211AMH30 0359
146.6TB
0MWL
210.3FM
0MWM
10.5CM
0AMH30 0360
10.6FM
120.2TB
4.4CM
161.4TB
205.4TB

Properties (7)

additional_info
630074081221202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-13T01:44:22-07:00
documentation
PROPIPE
is_lateral_inspection
false