Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 04:41 AM
  • 15 0419_15 0934_08242021_215600.mp4

Date
08/24/2021
W/O
906618
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00607
PipeID
P12345
Time
9:41 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9331
Sewer Name
15 HILL DRIVE EXTENSION TRUNK
City
ROSEMEAD
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_906618_TV15221_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0419
Downstream MH
15 0934
Dir. of Survey
Downstream
Length Surveyed
281.3 ft.
Total Length
281.3 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
120
O&M Index
1
O&M Quick
1300
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
123
Pipe schematic from manhole 15 0419 to 15 0934
MH: 15 0419MH: 15 0934downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 04190 ft. MWM - Water Mark, 20 %of cross sectional area40.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES53.5 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES58.5 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES67.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"78.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES78.6 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES84 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"89.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"178.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"251.8 ft. TF - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"268.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK281.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0934

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    40.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    67.6 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    78.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

    78.6 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    89.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    178.1 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
281.3CM
178.1TBA
268.6TF
165.5TFC
251.8TF
67.6TBA
58.5RFJ
78.6CM
0MWL
0AMH15 0419
40.4CM
89.3CM
281.3MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
84TFC
78.6RFJ
53.5RFJ
281.3AMH15 0934

Properties (7)

additional_info
630074082421201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-08-24T21:41:40-07:00
documentation
PROPIPE
is_lateral_inspection
false