Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 11:09 AM
Date
01/25/2018
W/O
684977
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00597
PipeID
P12326
Time
3:09 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5175
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
WO_684977_TV15013_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0403
Downstream MH
15 0402
Dir. of Survey
Downstream
Length Surveyed
252.8 ft.
Total Length
252.8 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0403 to 15 0402
MH: 15 0403MH: 15 0402downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 04032 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"51.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"60.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"109.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"111.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES150 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"159.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"202.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"211.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"234 ft. FM - Fracture Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES250.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish250.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish252.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0402252.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observations (20)

DistanceCodeObservation
252.8AMH15 0402
8.1TFC
60.9TFC
159.2TFC
0MWM
2DAGS
0MWL
211.9TFC
111.6FM
100.6TFC
250.4DAGS
109.8TFC
250.4CM
0AMH15 0403
2CM
51.5TFC
234FM
150TFC
252.8MGOCONNECTION AT MH 3 O'CLOCK
202.8TFC

Properties (6)

additional_info
SC347015
custom_field_two
3
customer
LACSD
datetime
2018-01-25T03:09:14-08:00
documentation
PROPIPE
is_lateral_inspection
false