Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 09:21 AM
Date
01/25/2018
W/O
684977
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00597
PipeID
P12320
Time
1:21 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5175
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
WO_684977_TV15013_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0397
Downstream MH
15 0396
Dir. of Survey
Downstream
Length Surveyed
118.4 ft.
Total Length
118.4 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0397 to 15 0396
MH: 15 0397MH: 15 0396downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 03972 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start9.1 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES14.2 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Start - CIP17.8 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Finish - CIP20.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"25.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES26.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"27.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES72.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"73.8 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Start - CIP79 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Finish - CIP116.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish116.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish118.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0396

Observations (17)

DistanceCodeObservation
79RPLCIP
17.8RPLCIP
14.2RPLCIP
25.2CM
118.4AMH15 0396
0MWM
0MWL
116.5DAGS
72.5TFC
9.1CS
27.8CM
2DAGS
20.3TFC
26.2TFC
0AMH15 0397
73.8RPLCIP
116.5CM

Properties (6)

additional_info
SC347015
custom_field_two
3
customer
LACSD
datetime
2018-01-25T01:21:43-08:00
documentation
PROPIPE
is_lateral_inspection
false