Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 09:52 AM
Date
01/25/2018
W/O
684977
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00597
PipeID
P12318
Time
1:52 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5175
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTERREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
WO_684977_TV15013_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0395
Downstream MH
15 0394
Dir. of Survey
Downstream
Length Surveyed
99 ft.
Total Length
99 ft.
Structural Index
3
Structural Quick
4233
Structural Rating
17
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 15 0395 to 15 0394
MH: 15 0395MH: 15 0394downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 03952 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"34.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish45.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"47.6 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES57.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES58.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"66.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.5 ft. FM - Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES96.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"96.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish99 ft. AMH - Downstream Manhole, Survey Ends - 15 0394

Observations (17)

DistanceCodeObservation
96.1TFC
45.9TFC
99AMH15 0394
5.5CM
0MWL
82.5FM
58.8TFC
66.9CM
96.5CM
47.6CM
34.8CM
57.8FM
96.5DAGS
2DAGS
9.7TFC
0MWM
0AMH15 0395

Properties (6)

additional_info
SC347015
custom_field_two
3
customer
LACSD
datetime
2018-01-25T01:52:20-08:00
documentation
PROPIPE
is_lateral_inspection
false