Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2021, 05:25 PM
  • LN 0009_LN 0008_09232021_103228.mp4

Date
09/23/2021
W/O
URGENT
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01232
PipeID
P26754
Time
10:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9134
Sewer Name
14 LNWRP PLANT SEWERS
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
01
Purpose
Routine Assessment
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
LN 0009
Downstream MH
LN 0008
Dir. of Survey
Downstream
Length Surveyed
232.4 ft.
Total Length
232.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole LN 0009 to LN 0008
MH: LN 0009MH: LN 0008downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - LN 0009124.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 10"231 ft. MGO - General Observation - Surface Spalling throughout the reach, 9 to 3 oclock232.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK232.4 ft. AMH - Downstream Manhole, Survey Ends - LN 0008

Observations (8)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MWL
0AMHLN 0009
232.4MGOCONNECTION AT MH 9 O'CLOCK
231MGOSurface Spalling throughout the reach, 9 to 3 oclock
124.7TF
232.4AMHLN 0008

Properties (7)

additional_info
630138092321051
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2021-09-23T10:25:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false