Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2021, 05:33 PM
  • LN 0008_LN 0007_09232021_104225.mp4

Date
09/23/2021
W/O
URGENT
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01232
PipeID
P26753
Time
10:33 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9134
Sewer Name
14 LNWRP PLANT SEWERS
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
01
Purpose
Routine Assessment
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
LN 0008
Downstream MH
LN 0007
Dir. of Survey
Downstream
Length Surveyed
299.5 ft.
Total Length
299.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole LN 0008 to LN 0007
MH: LN 0008MH: LN 0007downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - LN 0008125.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 8"298 ft. MGO - General Observation - Surface Spalling throughout, from 9 to 3 oclock299.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK299.5 ft. AMH - Downstream Manhole, Survey Ends - LN 0007

Observations (8)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
299.5MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0AMHLN 0008
299.5AMHLN 0007
298MGOSurface Spalling throughout, from 9 to 3 oclock
125.9TFA

Properties (7)

additional_info
630138092321051
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2021-09-23T10:33:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false