Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2021, 10:33 AM
  • 02 0896_02 0895_9252021_033446.mp4

Date
09/25/2021
W/O
0915984
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00252
PipeID
P03464
Time
3:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1953
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20210924MDM_DOWNEY_BELLFLOWER_DIVERSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0896
Downstream MH
02 0895
Dir. of Survey
Downstream
Length Surveyed
347.4 ft.
Total Length
347.4 ft.
Structural Index
2
Structural Quick
3B2D
Structural Rating
97
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
97
Pipe schematic from manhole 02 0896 to 02 0895
MH: 02 0896MH: 02 0895downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM2 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE8 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE13.5 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES, Finish - SLIGHT13.5 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish - SLIGHT15.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT15.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H15.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT20.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H20.6 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT24.9 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish - SLIGHT36.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - H43.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - H45.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H45.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H60.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H86.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H86.6 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H96.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES117.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H117.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES126.7 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start - H127.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H132.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H136.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Finish - H138.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start - H143.1 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish - H158.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - HH158.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - S163.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H168.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H173.9 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H184 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H199.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL214.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL224.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H234.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SL241.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - SL241.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish250.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H255.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H259.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H270.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H275.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H280.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H290.9 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT290.9 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - H296.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO296.2 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish - H331.9 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H347.4 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (6)

  • Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    2 ft. - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE

    8 ft. - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE

  • Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H

    127.1 ft. - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

    199.4 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SL

    234.3 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    290.9 ft. - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

Observations (54)

DistanceCodeObservation
15.6FCSLIGHT
296.2FL
158.1FCHH
45.6FLH
15.6FLH
24.9FCSLIGHT
280.9FCH
296.2FCH
199.4FLSL
13.5FCSLIGHT
36.1FCH
347.4AMH5:00AM
20.6FLH
184FCH
86.6FLH
127.1FCH
136.1FLH
259.4FLH
117.6FL
138.3FLH
234.3FCSL
45.6FLH
0MWM
0MWL
255.6FLH
20.6FCSLIGHT
250.1FCH
270.7FCH
96.8FC
241.1FCSL
43.2FCH
13.5FCSLIGHT
126.7FLH
86.6FCH
8FCSLIGHT
173.9FCH
290.9FCSLIGHT
168.8FLH
143.1FLH
15.6FLSLIGHT
8FCHAIRLINE
241.1FL
60.4FLH
290.9FCH
0AMH4:15AM
224.5FLH
275.4FLH
331.9FCH
2FCHAIRLINE
132.8FCH
163.4FCH
117.5FCH
214.7FCSL
158.6FLS

Properties (6)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2021-09-25T03:33:55-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false