G 0115_G 0114_9152021_033035.mp4
2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & BROKEN
2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
2 ft. - General Observation - 80% MISSING TILES
4.8 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR
19.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING LONG CIRCM REBAR
32.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR
153.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR HANGING
187.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING REBAR
236.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR
| Distance | Code | Observation |
|---|---|---|
| 2 | SRC | LONG CIRCUM REBAR CORRODED & BROKEN |
| 300.4 | SRC | LONG CIRCM REBAR BROKEN & MISSING |
| 32.2 | SRC | BROKEN MISSING REBAR |
| 0 | AMH | 3:25AM |
| 0 | MWL | — |
| 187.7 | SRC | BROKEN HANGING REBAR |
| 0 | MGO | Conn. @ Mh, 9 O' Clock. Active |
| 4.8 | SRC | BROKEN CIRCUM REBAR |
| 2 | SSS | BLISTERING PEELING CONCRETE |
| 300.4 | SAM | SEVERE AGG |
| 300.4 | SRC | LONG CIRCUM REBAR CORRODED & MISSING |
| 0 | MWM | — |
| 2 | SAM | SEVERE AGG |
| 2 | MGO | 80% MISSING TILES |
| 19.3 | SRC | BROKEN MISSING LONG CIRCM REBAR |
| 300.8 | AMH | 3:55AM |
| 236.6 | SRC | BROKEN HANGING CIRCUM REBAR |
| 300.4 | SSS | BLISTERING PEELING CONCRETE |
| 153.6 | SRC | BROKEN CIRCUM REBAR HANGING |