Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2021, 07:37 AM
  • G 0116_G 0115_9152021_015703.mp4

Date
09/15/2021
W/O
0901312
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01443
Time
12:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1942
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20210913MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0116
Downstream MH
G 0115
Dir. of Survey
Downstream
Length Surveyed
542.7 ft.
Total Length
542.7 ft.
Structural Index
5
Structural Quick
5741
Structural Rating
41
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
46
Pipe schematic from manhole G 0116 to G 0115
MH: G 0116MH: G 0115downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 80 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MGO - General Observation - 70% MISSING TILES START0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE28.6 ft. MGO - General Observation - 70% MISSING TILES59 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING72.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - MISSING LONG CIRCUM REBAR132.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR147.8 ft. MGO - General Observation - 48" NRCP202.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR213.7 ft. MWL - Water Level, 60 %of cross sectional area227 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUN REBAR456.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR542.4 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED BROKEN MISSING542.4 ft. MGO - General Observation - 70% MISSING TILES542.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE542.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG542.7 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (11)

  • General Observation - 70% MISSING TILES START

    0 ft. - General Observation - 70% MISSING TILES START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 70% MISSING TILES

    28.6 ft. - General Observation - 70% MISSING TILES

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

    59 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR

    132.6 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR

  • General Observation - 48" NRCP

    147.8 ft. - General Observation - 48" NRCP

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING  CIRCUM REBAR

    202.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUN REBAR

    227 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR

    456.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN HANGING CIRCUM REBAR

Observations (23)

DistanceCodeObservation
542.4SRCLONG CIRCUM REBAR CORRODED BROKEN MISSING
542.7AMH3:05AM
0MWM
2SAMSEVERE AGG
0MWL
72.2SRCMISSING LONG CIRCUM REBAR
456.2SRCBROKEN HANGING CIRCUM REBAR
542.4MGO70% MISSING TILES
2SRCLONG CIRCUM REBAR CORRODED & MISSING
0MGOConn. @ Mh, 9 O' Clock. Active
202.7SRCBROKEN HANGING CIRCUM REBAR
0AMH1:55AM
132.6SRCBROKEN HANGING CIRCUM REBAR
59SRCLONG CIRCUM REBAR CORRODED & MISSING
213.7MWL
0MGO70% MISSING TILES START
147.8MGO48" NRCP
28.6MGO70% MISSING TILES
0MGOConn. @ Mh, 3 O' Clock. OPEN
542.4SSSBLISTERING PEELING CONCRETE
227SRCBROKEN HANGING CIRCUN REBAR
2SSSBLISTERING PEELING CONCRETE
542.4SAMSEVERE AGG

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED BROKEN MISSING HANGING
custom_field_two
1
customer
LACSD
datetime
2021-09-15T00:37:57-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false