Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2021, 11:37 AM
  • G 0117_G 0116_9142021_044033.mp4

Date
09/14/2021
W/O
0901312
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01444
Time
4:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1942
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20210913MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0117
Downstream MH
G 0116
Dir. of Survey
Downstream
Length Surveyed
527.8 ft.
Total Length
527.8 ft.
Structural Index
4
Structural Quick
5241
Structural Rating
16
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
21
Pipe schematic from manhole G 0117 to G 0116
MH: G 0117MH: G 0116downstream0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG BCIRCUM REBAR CORRODED & MISSING2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG GREASE COAT 20% START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - 80% TILES MISSING START7.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR MISSING421.4 ft. MGO - General Observation - 50% MISSING TILES START527.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG527.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED & MISSING527.3 ft. MGO - General Observation - 70% MISSING TILES FINISH527.3 ft. MGO - General Observation - MAG GREASE COAT 20% FINISH527.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE527.8 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (7)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG BCIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG BCIRCUM REBAR CORRODED & MISSING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG GREASE COAT 20% START

    2 ft. - General Observation - MAG GREASE COAT 20% START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 80% TILES MISSING START

    2 ft. - General Observation - 80% TILES MISSING START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR MISSING

    7.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR MISSING

  • General Observation - 50% MISSING TILES START

    421.4 ft. - General Observation - 50% MISSING TILES START

Observations (16)

DistanceCodeObservation
527.3SAMSEVERE AGG
0MWL
0AMH4:40AM
527.3SRCLONG CIRCUM REBAR CORRODED & MISSING
0MWM
2SRCLONG BCIRCUM REBAR CORRODED & MISSING
2SSSBLISTERING PEELING CONCRETE
2MGOMAG GREASE COAT 20% START
527.3MGO70% MISSING TILES FINISH
2SAMSEVERE AGG
527.3MGOMAG GREASE COAT 20% FINISH
2MGO80% TILES MISSING START
527.3SSSBLISTERING PEELING CONCRETE
527.8AMH5:15AM
7.9SRCLONG CIRCUM REBAR MISSING
421.4MGO50% MISSING TILES START

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2021-09-14T04:37:09-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false