Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2021, 11:02 AM
  • G 0114_G 0113_9152021_042102.mp4

Date
09/15/2021
W/O
0901312
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01441
Time
4:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1943
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20210913MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0114
Downstream MH
G 0113
Dir. of Survey
Downstream
Length Surveyed
293.7 ft.
Total Length
293.7 ft.
Structural Index
4
Structural Quick
5541
Structural Rating
31
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
36
Pipe schematic from manhole G 0114 to G 0113
MH: G 0114MH: G 0113downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - 90% MISSING TILES2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING25.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED MISSING75.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN HANGING REBAR125.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR188.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR293.2 ft. MGO - General Observation - 90% MISSING TILES FINISH293.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - REBA BROKEN & HANGING293.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED & MISSING293.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active293.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active293.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE293.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG293.7 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (8)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 90% MISSING TILES

    2 ft. - General Observation - 90% MISSING TILES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED MISSING

    25.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED MISSING

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN HANGING REBAR

    75.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    125.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    188.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (19)

DistanceCodeObservation
0AMH4:20AM
293.2MGO90% MISSING TILES FINISH
293.2SRCREBA BROKEN & HANGING
293.7AMH4:40AM
75.2SRCBROKEN HANGING REBAR
293.2SRCLONG CIRCUM REBAR CORRODED & MISSING
0MWL
125.1SRCBROKEN REBAR
293.2MGOConn. @ Mh, 3 O' Clock. Active
293.2MGOConn. @ Mh, 9 O' Clock. Active
2SAMSEVERE AGG
0MWM
2MGO90% MISSING TILES
25.9SRCLONG CIRCUM REBAR CORRODED MISSING
293.2SSSBLISTERING PEELING CONCRETE
293.2SAMSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
188.7SRCBROKEN REBAR
2SRCLONG CIRCUM REBAR CORRODED & MISSING

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED BROKEN MISSING HANGING
custom_field_two
1
customer
LACSD
datetime
2021-09-15T04:02:02-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false