Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 04:59 AM
  • A 1102_H 0994_08122021_221417.mp4

Date
08/12/2021
W/O
906779
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01005
PipeID
P15409
Time
9:59 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9117
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_906779_TV21087_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
A 1102
Downstream MH
H 0994
Dir. of Survey
Downstream
Length Surveyed
321.5 ft.
Total Length
321.5 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
126
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
128
Pipe schematic from manhole A 1102 to H 0994
MH: A 1102MH: H 0994downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 11020 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. MGO - General Observation - 90% MAG COAT2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start77.2 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"126.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN196.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN309.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN319.5 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish321 ft. MGO - General Observation - ROACHES @ MH321.5 ft. AMH - Downstream Manhole, Survey Ends - H 0994

Observation photos (6)

  • General Observation - 90% MAG COAT

    2 ft. - General Observation - 90% MAG COAT

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    77.2 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    126.9 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    196.6 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    309.5 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

Observations (12)

DistanceCodeObservation
319.5SSS
196.6TBOPEN
0MWL
2MGO90% MAG COAT
321MGOROACHES @ MH
2SSS
321.5AMHH 0994
77.2TBC
309.5TBOPEN
0AMHA 1102
126.9TBOPEN
0MWM

Properties (7)

additional_info
630138081221201
custom_field_three
MAG COAT, SPALLING
custom_field_two
3
customer
1
datetime
2021-08-12T21:59:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false