Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 07:25 AM
  • H 0990_21 0215_08132021_003024.mp4

Date
08/13/2021
W/O
906779
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01005
PipeID
P15404
Time
12:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9117
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_906779_TV21087_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0990
Downstream MH
21 0215
Dir. of Survey
Downstream
Length Surveyed
17.5 ft.
Total Length
17.5 ft.
Structural Index
3
Structural Quick
3323
Structural Rating
15
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
21
Pipe schematic from manhole H 0990 to 21 0215
MH: H 0990MH: 21 0215downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - H 09900 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 35% MAG COAT2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish15.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish15.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish17 ft. MGO - General Observation - ROACHES @ MH17.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN17.5 ft. AMH - Downstream Manhole, Survey Ends - 21 0215

Observation photos (3)

  • General Observation - 35% MAG COAT

    2.1 ft. - General Observation - 35% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
15.5SSS
0MGOCONN @ MH 9 O'CLOCK/OPEN
0MWM
2.1MGO35% MAG COAT
15DAGS
0MGOCONN @ MH 9 O'CLOCK/CAPPED
15.5SAV
2DAGS
0AMHH 0990
17MGOROACHES @ MH
17.5MGOCONN @ MH 3 O'CLOCK/UNKNOWN
2.1SSS
2.1SAV
0MWL
17.5AMH21 0215

Properties (7)

additional_info
630138081221201
custom_field_three
MAG COAT, SPALLING, AGGREGATE VISBLE
custom_field_two
3
customer
1
datetime
2021-08-13T00:25:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false