- Date
- 08/17/2021
- W/O
- 906779
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z01005
- PipeID
- P15365
- Time
- 9:56 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9255
- Sewer Name
- H JOINT OUTFALL H - UNIT 7C
- City
- CITY OF INDUSTRY
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 34
- Purpose
- Routine Assessment
- Project
- RFIR_WO_906779_TV21087_AUG2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Width
- 36 in.
- Upstream MH
- H 0951
- Downstream MH
- H 1058
- Dir. of Survey
- Upstream
- Length Surveyed
- 31.9 ft.
- Total Length
- 31.9 ft.
- Structural Index
- 3
- Structural Quick
- 5536
- Structural Rating
- 53
- O&M Index
- 2
- O&M Quick
- 2500
- O&M Rating
- 10
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 63
Pipe schematic from manhole H 0951 to H 1058 Observation photos (3)

2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

7 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start