Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2021, 10:16 AM
  • J 0142_J 0141_08162021_040916.mp4

Date
08/16/2021
W/O
906774
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00052
PipeID
P11375
Time
3:16 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9320
Sewer Name
J JOINT OUTFALL J - UNIT 1A
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_906774_TV05352_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
J 0142
Downstream MH
J 0141
Dir. of Survey
Downstream
Length Surveyed
312.2 ft.
Total Length
312.2 ft.
Structural Index
3
Structural Quick
4D3K
Structural Rating
283
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
283
Pipe schematic from manhole J 0142 to J 0141
MH: J 0142MH: J 0141downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 01420 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area5.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start149 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish193.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES312.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312.2 ft. AMH - Downstream Manhole, Survey Ends - J 0141

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    193.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
5.3CM
149FM
312.2CM
0AMHJ 0142
193.4FM
0MWL
312.2AMHJ 0141
28.5FM
0MWM

Properties (7)

additional_info
630074081621003
custom_field_three
MULTIPLE CRACKS/ FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-16T03:16:19-07:00
documentation
PROPIPE
is_lateral_inspection
false