Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2021, 08:06 AM
  • 03 0551_03 0055_08182021_012204.mp4

Date
08/18/2021
W/O
906707
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00366
PipeID
P05076
Time
1:06 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9326
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_906707_TV03159_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
03 0551
Downstream MH
03 0055
Dir. of Survey
Downstream
Length Surveyed
284.5 ft.
Total Length
284.5 ft.
Structural Index
3
Structural Quick
4D3G
Structural Rating
231
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
231
Pipe schematic from manhole 03 0551 to 03 0055
MH: 03 0551MH: 03 0055downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 03 05510 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start23.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"31 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish31 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"143 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start143 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish151.1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start210.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish284.5 ft. AMH - Downstream Manhole, Survey Ends - 03 0055284.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    31 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    67.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    143 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    151.1 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
67.7FM
23.8TFC
31FL
284.5AMH03 0055
67.7CM
31CM
0MWL
96.3TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
284.5CM
0AMH03 0551
2.1FL
143CM
143FM
151.1FM
0MWM
210.5FM

Properties (7)

additional_info
630074081721203
custom_field_three
MULTIPLE FRACTURE'S/CRACKS
custom_field_two
2
customer
1
datetime
2021-08-18T01:06:41-07:00
documentation
PROPIPE
is_lateral_inspection
false