Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2021, 08:46 AM
  • 03 0038_03 0037_08182021_015647.mp4

Date
08/18/2021
W/O
906707
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00366
PipeID
P05058
Time
1:46 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9326
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_906707_TV03159_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
03 0038
Downstream MH
03 0037
Dir. of Survey
Downstream
Length Surveyed
324.6 ft.
Total Length
324.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 03 0038 to 03 0037
MH: 03 0038MH: 03 0037downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 00380 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED0 ft. MWM - Water Mark, 35 %of cross sectional area7.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.1 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.6 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.9 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.7 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"200 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.2 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324.6 ft. AMH - Downstream Manhole, Survey Ends - 03 0037

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    10.1 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    66.6 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    122.9 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    163.7 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    200 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    246.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    303.2 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
163.7TS
324.6CM
7.6CM
0AMH03 0038
66.6TS
0MWL
303.2TS
324.6AMH03 0037
122.9TS
10.1TS
200TS
0MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
246.2TB
0MWM

Properties (7)

additional_info
630074081721203
custom_field_three
multiple cracks
custom_field_two
3
customer
1
datetime
2021-08-18T01:46:05-07:00
documentation
PROPIPE
is_lateral_inspection
false