Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2021, 06:54 AM
  • 05 0783_05 0782_08182021_000600.mp4

Date
08/17/2021
W/O
906567
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00553
PipeID
P06011
Time
11:54 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9325
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_906567_TV05202_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
05 0783
Downstream MH
05 0782
Dir. of Survey
Downstream
Length Surveyed
409.4 ft.
Total Length
409.4 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
324
O&M Index
4
O&M Quick
4300
O&M Rating
12
Overall Index
4
Overall Quick
Overall Rating
336
Pipe schematic from manhole 05 0783 to 05 0782
MH: 05 0783MH: 05 0782downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07830 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area5.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start345.5 ft. MCU - Camera Underwater, Start360.5 ft. MCU - Camera Underwater, Finish366.5 ft. MGO - General Observation - BREAK @ JOINT - 11 TO 12 O'CLOCK409.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0782409.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Camera Underwater, Start

    345.5 ft. - Camera Underwater, Start

Observations (9)

DistanceCodeObservation
0AMH05 0783
366.5MGOBREAK @ JOINT - 11 TO 12 O'CLOCK
409.4AMH05 0782
360.5MCU
345.5MCU
0MWM
5.8FM
409.4FM
0MWL

Properties (7)

additional_info
630074081721202
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-08-17T23:54:32-07:00
documentation
PROPIPE
is_lateral_inspection
false