Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2021, 10:16 AM
  • 18 0369_18 0368_972021_033713.mp4

Date
09/07/2021
W/O
0911299
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00690
PipeID
P14203
Time
3:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1935
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Capital Improvement Program Assesment
Project
20210907MDM_NORTH_NORWALK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0369
Downstream MH
18 0368
Dir. of Survey
Downstream
Length Surveyed
134.3 ft.
Total Length
134.3 ft.
Structural Index
2
Structural Quick
432E
Structural Rating
72
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
72
Pipe schematic from manhole 18 0369 to 18 0368
MH: 18 0369MH: 18 0368downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.9 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT7.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE11.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL11.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL15.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - H19.5 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H23.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL27.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL32 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H35.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL39.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL39.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H44.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open51.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL54.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H54.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H59.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL63.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL67.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H71.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H75.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H79.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL84 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL88 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL92.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL96.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL100.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL103.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H108.8 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL112.7 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H117 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLO120.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H124.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL128.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H134.3 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observations (38)

DistanceCodeObservation
92.4FCSL
108.8FCSL
32FCH
0AMH3:20AM
11.4FCSL
67.5FCH
39.9FCSL
51.3FMSL
63.2FCSL
117FCSLO
71.3FCH
0MWL
7.7FMHAIRLINE
54.9FCH
11.4FCSL
0MWM
128.7FCH
2.9FCSLIGHT
103.9FCH
54.9FCH
84FCSL
124.7FCSL
100.5FCSL
79.5FCSL
120.9FCH
44.5TFOpen
39.9FCH
59.2FCSL
27.7FCSL
75.7FCH
88FCSL
96.3FCSL
134.3AMH3:55AM
19.5FCH
15.4FMH
35.7FCSL
112.7FCH
23.5FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
2
customer
LACSD
datetime
2021-09-07T03:16:39-07:00
documentation
MARTIN,CASTILLO
is_lateral_inspection
false