Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2021, 08:11 AM
  • 18 0829_18 0828A_08032021_012401.mp4

Date
08/03/2021
W/O
906773
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00707
PipeID
P14693
Time
1:11 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8697
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_906773_TV18113_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0828A
Downstream MH
18 0829
Dir. of Survey
Upstream
Length Surveyed
195.3 ft.
Total Length
195.3 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0828A to 18 0829
MH: 18 0828AMH: 18 0829upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 08290 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK1.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish115.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"191 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start195.3 ft. MGO - General Observation - MH IS ABANDONED195.3 ft. MWL - Water Level, 5 %of cross sectional area195.3 ft. AMH - Downstream Manhole, Survey Begins - 18 0828A195.3 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
195.3AMH18 0829
31.5TFC
195.3MGOCONNECTION AT MH 3 O'CLOCK CAPPED
78TFC
0MGOMH IS ABANDONED
0MWL
4.3FM
193.9FM
34.1TFC
0AMH18 0828A
195.3MGOCONNECTION AT MH 9 O'CLOCK
80.1TFC
0MWM

Properties (7)

additional_info
630138080221202
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-08-03T01:11:24-07:00
documentation
PROPIPE
is_lateral_inspection
false