Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2021, 07:58 AM
  • 01 1015_01 1014_08192021_010229.mp4

Date
08/19/2021
W/O
906735
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00223
PipeID
P01860
Time
12:58 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9328
Sewer Name
01 VERNON EXTENSION RELIEF TRUNK
City
VERNON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_906735_TV01228_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 1014
Downstream MH
01 1015
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 01 1014 to 01 1015
MH: 01 1014MH: 01 1015upstream0 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - flow high0 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. AMH - Downstream Manhole, Survey Begins - 01 10142.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.1 ft. MWL - Water Level, 40 %of cross sectional area2.1 ft. MWM - Water Mark, 50 %of cross sectional area2.1 ft. MGO - Reversal Inspection

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 15 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    2.1 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0AMH01 1014
2.1SRV
0MGOCONNECTION AT THE MH 9 OC'LOCK
2.1MSAflow high
0MWL
0MWM
0MGO
2.1DAGS
2.1SAV

Properties (7)

additional_info
630074081821201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-08-19T00:58:34-07:00
documentation
PROPIPE
is_lateral_inspection
false