Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 06:18 AM
  • 01 0230A_01 0230_08242021_234217.mp4

Date
08/24/2021
W/O
906572
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01273
Time
11:18 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9333
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_906572_TV01222_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
01 0230A
Downstream MH
01 0230
Dir. of Survey
Downstream
Length Surveyed
272.2 ft.
Total Length
272.2 ft.
Structural Index
3
Structural Quick
4C3K
Structural Rating
362
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
362
Pipe schematic from manhole 01 0230A to 01 0230
MH: 01 0230AMH: 01 0230downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0230A0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start85.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish127.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"133 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES143.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES163.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.2 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES180.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES203.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES234.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"246.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.3 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES272 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish272.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish272.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0230

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    136.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    143.9 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    164.2 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    189.5 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    227.6 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    268.3 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
189.5FL
203.6TF
227.6FL
0MWM
234.1TF
272SAV
0AMH01 0230A
7.8FM
164.2FM
136.3FL
2.1SSS
85.4TF
127.6TF
272.2SSS
96.7FM
0MWL
133TF
87.6TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
143.9FL
259.7TF
180.8TF
163.1TF
268.3FM
272.2AMH01 0230
206.8TF
2.1SAV
246.9TF

Properties (7)

additional_info
630074082421203
custom_field_three
AGGREGATE VISIBLE/MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-24T23:18:49-07:00
documentation
PROPIPE
is_lateral_inspection
false