Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2021, 10:34 AM
  • 05 1385_05 1384_08172021_034950.mp4

Date
08/17/2021
W/O
906612
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06605
Time
3:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9323
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_906612_TV05336_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
8 in.
Upstream MH
05 1385
Downstream MH
05 1384
Dir. of Survey
Downstream
Length Surveyed
315.9 ft.
Total Length
315.9 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
252
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
254
Pipe schematic from manhole 05 1385 to 05 1384
MH: 05 1385MH: 05 1384downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 13850 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES5.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES251.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"315.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1384

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    250.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
315.9FM
0AMH05 1385
0MGOCONNECTION AT THE MH 9 OC'LOCK
250.6DAGS
3.1FM
0MWL
191.5TF
234.4TFC
39.5TFC
251.7TFA
85.3TFC
0MWM
0MGOCONNECTION AT THE MH 3 OC'LOCK
5.3FM
315.9AMH05 1384

Properties (7)

additional_info
630074081621203
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-17T03:34:08-07:00
documentation
PROPIPE
is_lateral_inspection
false