Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2021, 04:59 AM
  • 18 0827_18 0826_08022021_221531.mp4

Date
08/02/2021
W/O
906569
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00707
PipeID
P14690
Time
9:59 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8696
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_906569_TV18119_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0826
Dir. of Survey
Downstream
Length Surveyed
94.9 ft.
Total Length
94.9 ft.
Structural Index
3
Structural Quick
4235
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 18 0827 to 18 0826
MH: 18 0827MH: 18 0826downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08274.1 ft. FS - Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES9.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES12.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES15.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES18.2 ft. FS - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES21.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK94.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0826

Observation photos (7)

  • Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    4.1 ft. - Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    9.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    12.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    15.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

    18.2 ft. - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
85TFC
94.9AMH18 0826
18.2FS
21.4FM
94.8MGOCONNECTION AT MH 3 O'CLOCK
15.2FM
6CM
35.4TFC
0MWM
9.2CM
4.1FS
0MWL
32.2TF
93FM
81.9TFC
12.1CM
0AMH18 0827

Properties (7)

additional_info
630138080221201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-08-02T21:59:21-07:00
documentation
PROPIPE
is_lateral_inspection
false