Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2021, 10:11 AM
  • 22 0958_22 0957_08102021_033544.mp4

Date
08/10/2021
W/O
906375
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00790
PipeID
P17328
Time
3:11 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9111
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_906375_TV22002_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0958
Downstream MH
22 0957
Dir. of Survey
Downstream
Length Surveyed
442.8 ft.
Total Length
442.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0958 to 22 0957
MH: 22 0958MH: 22 0957downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 09580 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS91.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS100 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS139.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS188.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS236.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS240.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"289.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS327.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"338.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS354.7 ft. LR - Alignment Right, 10 %, Start374.2 ft. LR - Alignment Right, 10 %, Finish395.7 ft. LR - Alignment Right, 15 %, Start421.1 ft. LR - Alignment Right, 15 %, Finish441.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish442.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK442.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0957

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 10 %, Start

    354.7 ft. - Alignment Right, 10 %, Start

  • Alignment Right, 15 %, Start

    395.7 ft. - Alignment Right, 15 %, Start

Observations (21)

DistanceCodeObservation
139.8TFCDEBRIS
236.5TFCDEBRIS
0AMH22 0958
374.2LR
338.5TFCDEBRIS
100TFCDEBRIS
38.7TFCDEBRIS
2.5SAV
289.7TFCDEBRIS
327.1TF
0MWM
91.5TFCDEBRIS
188.4TFCDEBRIS
442.8MGOCONNECTION AT MH 9 O'CLOCK
395.7LR
441.3SAV
442.8AMH22 0957
354.7LR
0MWL
240.9TFC
421.1LR

Properties (7)

additional_info
630138080921201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-08-10T03:11:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false