Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2021, 08:07 PM
  • _29 0546_07262021_132801.mp4

Date
07/26/2021
W/O
901245
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01090
PipeID
P24655
Time
1:07 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9084
Sewer Name
29 ALAMITOS PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
WO_901245_TV29013_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0546
Dir. of Survey
Upstream
Length Surveyed
384.9 ft.
Total Length
384.9 ft.
Structural Index
2
Structural Quick
2O00
Structural Rating
156
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
308
Pipe schematic from manhole 29 0546 to unknown
MH: 29 0546MH: upstream0 ft. AEP - End of Pipe0.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish22.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES23.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"57.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN81.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN144.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN147.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"155.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"216.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"245.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN279.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"281.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES342.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"345.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"382.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start382.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start384.9 ft. MWM - Water Mark, 10 %of cross sectional area384.9 ft. MGO - General Observation - ROACHES @ MH384.9 ft. MWL - Water Level, 5 %of cross sectional area384.9 ft. AMH - Downstream Manhole, Survey Begins - 29 0546

Observation photos (6)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    98.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    139.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

    229.8 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    290.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    362.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • End of Pipe

    384.9 ft. - End of Pipe

Observations (27)

DistanceCodeObservation
168.3TFC
0MWM
303.6TFC
384.1MGOCONN @ MH 9 O'CLOCK/CAPPED
384.9AEP
290.7TBOPEN
0MGOROACHES @ MH
0MWL
382DAGS
382SSS
240.7TFOPEN
98.3CL
2SSS
103.1TFC
139.2TBOPEN
384.1TFA
237.8TFC
229.8TBA
327.7TFOPEN
165.7TFA
42.2TFA
2DAGS
39.6TFC
0AMH29 0546
362.1CL
105.3TFC
361.2TFA

Properties (7)

additional_info
630074072621061
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-07-26T13:07:14-07:00
documentation
PROPIPE
is_lateral_inspection
false