Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2021, 09:35 AM
  • E 0041_E 0040_08122021_025316.mp4

Date
08/12/2021
W/O
906380
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11268
Time
2:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9313
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_906380_TV01123_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0041
Downstream MH
E 0040
Dir. of Survey
Downstream
Length Surveyed
623.9 ft.
Total Length
623.9 ft.
Structural Index
3
Structural Quick
523X
Structural Rating
628
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
628
Pipe schematic from manhole E 0041 to E 0040
MH: E 0041MH: E 0040downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - E 00410 ft. MWL - Water Level, 25 %of cross sectional area3.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. MGO - General Observation - MAG COAT8.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start261.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES621.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO623.9 ft. AMH - Downstream Manhole, Survey Ends - E 0040623.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish623.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    261.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

    621.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
0MWM
0MGOCONNECTION AT THE MH 9 OC'LOCK
623.9AMHE 0040
621.3SRV
0AMHE 0041
0MWL
3.6SAV
623.9SAV
261.8SRV
8.5SSS
623.9SSS
3.6MGOMAG COAT

Properties (7)

additional_info
630074081121202
custom_field_three
AGGREGATE VISIBLE/SPALLING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-08-12T02:35:21-07:00
documentation
PROPIPE
is_lateral_inspection
false