Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2021, 09:53 AM
  • E 0040_E 0039_08122021_032215.mp4

Date
08/12/2021
W/O
906380
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11267
Time
2:53 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9313
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_906380_TV01123_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0040
Downstream MH
E 0039
Dir. of Survey
Downstream
Length Surveyed
759.4 ft.
Total Length
759.4 ft.
Structural Index
3
Structural Quick
513]
Structural Rating
760
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
760
Pipe schematic from manhole E 0040 to E 0039
MH: E 0040MH: E 0039downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00400.1 ft. MWM - Water Mark, 35 %of cross sectional area2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COAT37.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO759.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish759.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish759.4 ft. AMH - Downstream Manhole, Survey Ends - E 0039

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

    37.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
2.5SAV
2.5SSS
759.3SAV
759.3SSS
0.1MWM
759.4AMHE 0039
37.2SRV
2.5MGOMAG COAT
0MWL
0AMHE 0040

Properties (7)

additional_info
630074081121202
custom_field_three
AGGREGATE VISIBLE/SPALLING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-08-12T02:53:23-07:00
documentation
PROPIPE
is_lateral_inspection
false