Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 04:31 AM
  • E 0034_E 0033_08122021_220200.mp4

Date
08/12/2021
W/O
906380
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11260
Time
9:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9314
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_906380_TV01123_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0034
Downstream MH
E 0033
Dir. of Survey
Downstream
Length Surveyed
595.6 ft.
Total Length
595.6 ft.
Structural Index
3
Structural Quick
513W
Structural Rating
600
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
600
Pipe schematic from manhole E 0034 to E 0033
MH: E 0034MH: E 0033downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00342.4 ft. MGO - General Observation - MAG COAT2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start475.5 ft. SRV - Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: NO595.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish595.6 ft. AMH - Downstream Manhole, Survey Ends - E 0033595.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: NO

    475.5 ft. - Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
595.6SSS
2.4MGOMAG COAT
0MWM
595.6AMHE 0033
2.4SAV
595.6SAV
0MWL
0AMHE 0034
475.5SRV
2.4SSS

Properties (7)

additional_info
630074081221201
custom_field_three
AGGREGATE VISIBLE/SPALLING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-08-12T21:31:27-07:00
documentation
PROPIPE
is_lateral_inspection
false